Ball Float Steam Trap (FT14-Flange)
The FT14-F is ball float steam trap having stainless steel working internals and integral automatic air venting facility. The FT14-F can be maintained without disturbing the pipework.
Available types
FT14 (R-L) Horizontal connections with flow from right to left
FT14 (L-R) Horizontal connections with flow from left to right
Sizes and pipe connections
DN15,DN20,DN25
Flanged EN 1092 PN16, ANSI 150 and JIS/KS 10.
Material:
Body:A216 WCB
Bonnet:A216 WCB
Seat:Stainless Steel
Ball Float and Lever:Stainless Steel
Capacities
Capacities shown above are based on condensate at saturation temperature. When discharging sub-cooled condensate the air vent provides extra capacity. Under start-up conditions when the condensate is cold the internal thermostatic air vent will be open and provides additional capacity to the main valve. On 4.5 bar units this will provide a minimum of 50% increased capacity above the hot condensate figures shown. On 10 and 14 bar units this will be a minimum increase of 100% on the published capacity. The above table gives the minimum additional cold water capacities from the air vent.
Available types
FT14 (R-L) Horizontal connections with flow from right to left
FT14 (L-R) Horizontal connections with flow from left to right
Sizes and pipe connections
DN15,DN20,DN25
Flanged EN 1092 PN16, ANSI 150 and JIS/KS 10.
Limiting Condition | ||
Body design conditions | PN16 | |
16 bar g @ 100°C | ||
TMA Maximum allowable temperature | 250°C @ 13 bar g | |
Minimum allowable temperature | -10°C | |
PMO Maximum operating pressure for saturated steam service | 14 bar g | |
TMO Maximum operating temperature | 250°C @ 13 bar g | |
Minimum operating temperature | 0°C | |
PMX Maximum differential pressure | FT14-4.5 | 4.5 bar |
FT14-10 | 10 bar | |
FT14-14 | 14 bar | |
Designed for a maximum cold hydraulic test pressure of 24 bar g |
Material:
Body:A216 WCB
Bonnet:A216 WCB
Seat:Stainless Steel
Ball Float and Lever:Stainless Steel
Capacities